Analysis of the Impact of Load Imbalance on Neutral Current and Power Losses Caused by Neutral Current in Transformer 1, 30 MVA, 70/20 kV at Bungaran Substation

Authors

  • Abdul Azis Universitas PGRI Palembang
  • Perawati Universitas PGRI Palembang
  • Yudi Irwansi Universitas PGRI Palembang
  • Muhammad Rizal Universitas PGRI Palembang

DOI:

https://doi.org/10.62951/ijeemcs.v2i3.318

Keywords:

Imbalance, Load, Neutral Current, Power Losses, Transformer

Abstract

Power transformers are crucial in the electrical distribution system, and their operational stability is significantly affected by load imbalance among phases. Load imbalance can lead to the flow of neutral current through the neutral conductor, causing additional power losses in the transformer. This study analyzes the impact of load imbalance on neutral current and power losses at Transformer 1 (30 MVA capacity, 70/20 kV) at the Bungaran Substation. Data such as phase current, neutral current, and power losses were measured at 12:00 and 21:00. At 12:00, the transformer’s full-load current was 839.17 A with a loading of 28.44% and a load imbalance of 0.74%, resulting in a neutral current of 4.36 A (1.83% of load current). The power loss due to neutral current was 12.64 W (4.36×10-5 %), and the loss due to neutral current flowing to the ground was 760 W (2.62×10-3 %). At 21:00, the full-load current decreased to 834.46 A, with a loading of 29.36% and a higher load imbalance of 1.36%. This caused a neutral current of 7.94 A (3.24%), with a power loss of 41.90 W (1.43×10-4 %) and a ground power loss of 2.52 W (8.60×10-3 %). The power losses were minimal compared to the transformer’s capacity, having little effect on system efficiency. However, maintaining load balance is essential for system efficiency and transformer longevity.

References

Aini, Z., Mutari, E., Liliana, L., & Candra, O. (2021). Analysis of imbalance loads and losses based on the largest loading by 3 units of 3-phase distribution transformer. JTEV (Jurnal Teknik Elektro dan Vokasional), 7(1), 69-77. https://doi.org/10.24036/jtev.v7i1.111965

Arifin, M. Z., Amiruddin, M., & Margono, M. (2023). Power losses caused by load imbalance in the central building of PGRI Semarang University. Advance Sustainable Science, Engineering and Technology, 5(1), 0230103. https://doi.org/10.26877/asset.v5i1.13854

Azis, A., Nurdiana, N., & Lathifatun Nisa, U. (2018). Rugi-rugi daya pada transformator U. 019 PT. PLN (Persero) WS@ JB Rayon Ampera akibat ketidakseimbangan beban. Jurnal Ampere, 3(1), 177-184. https://doi.org/10.31851/ampere.v3i1.3475

Chen, J., Zhu, R., Liserre, M., & O'Donnell, T. (2018, May). Neutral current reduction control for smart transformer under the imbalanced load in distribution system. In 2018 13th IEEE Conference on Industrial Electronics and Applications (ICIEA) (pp. 2381-2386). IEEE. https://doi.org/10.1109/ICIEA.2018.8398108

Dendi, D., Azis, A., & Perawati, P. (2022). Analisa pengaruh pembebanan terhadap susut umur transformator daya 150 kV di PLTGU Keramasan Palembang. TEKNIKA: Jurnal Teknik, 9(1), 28-41. https://doi.org/10.35449/teknika.v9i1.198

Diao, G., Ni, H., Si, W., Gu, Y., & Yang, J. (2025). Multi-physics numerical research in oil-immersed three-phase transformer under load unbalance. Energies, 18(5), 1217. https://doi.org/10.3390/en18051217

Febrianti, I. K. (2018). Analisa sistem pentanahan transformator. Jurnal Ampere, 3(1), 185-201. https://doi.org/10.31851/ampere.v3i1.2146

Hartono, H., Sudjoko, R. I., Hariyadi, S., & Sukomardojo, T. (2025). Analysis of the effect of unbalanced load on neutral current, power losses and efficiency in distribution transformer. Journal of Research in Social Science and Humanities, 5(1). https://doi.org/10.47679/jrssh.v5i1.370

Irwansyah, D., Yandi, W., Sunanda, W., & Zakri, A. A. (2022). Distribution transformer load imbalance analysis at Universitas Bangka Belitung. Journal of Innovation and Technology, 3(1), 6. https://doi.org/10.31629/jit.v3i1.4333

Latupeirissa, H. L., & Titaley, G. V. (2023). Analysis of the effect of load imbalance on neutral current and power losses in distribution transformer Bglwy1036 substation Rumah Tiga. International Journal of Multi Science, 3(04), 178-190. https://multisciencejournal.com/index.php/ijm/article/view/343/278

Liliana, L., Aini, Z., & Bandri, S. (2024). Estimated cost of power losses due to imbalance, no-load and on-load on transformers in 2023-2033. Jurnal Edukasi Elektro, 8(1), 45-54. https://doi.org/10.21831/jee.v8i1.65224

Listiawati, D., & Andini, A. N. (2023). Analysis of the influence of load unbalance on the neutral current power loss in substation KP10 PT. PLN (Persero) UP3 Teluk Naga. International Journal of Advanced Multidisciplinary, 2(3), 690-702. https://doi.org/10.38035/ijam.v2i3.354

Pan, B., Zhang, Y., Gui, X., Wan, Y., & Wang, G. (2019, April). Analysis and research of three-phase unbalance in distribution transformers. In IOP Conference Series: Earth and Environmental Science (Vol. 252, No. 3, p. 032196). IOP Publishing. https://doi.org/10.1088/1755-1315/252/3/032196

PT PLN. (2014). Edaran Direksi PT PLN (Persero) Nomor: 0017. E/DIR/2014 Tentang Metode Pemeliharaan Trafo Distribusi Berbasis Kaidah Manajemen Aset. https://caridokumen.com/queue/pt-pln-persero-edaran-direksi-pt-pln-persero-_5a46cb27b7d7bc7b7a1f4c7e_pdf?queue_id=-1

Rizal, M., Azis, A., Emidiana, I. K. P., Al Amin, M. S., Nurdiana, N., & Perawati, Y. I. (2024). Analysis of load imbalance in Tarakan distribution transformer of PT PLN (Persero) Sukarami customer service unit. https://doi.org/10.47191/etj/v9i05.12

Siboro, D. A. S., Arsyad, M. I., & Junaidi, J. (2023). Analysis of transformer loading imbalance at the Faculty of Engineering, Tanjungpura University. Journal of Electrical Engineering, Energy, and Information Technology (J3EIT), 12(2), 385-395. https://doi.org/10.26418/j3eit.v12i2.77061

Styawan, T. A., & Rahmawati, Y. (2021). Load impact analysis towards power loss in distribution substation in Wlingi District. http://dx.doi.org/10.17977/um049v1i1p27-33

Syahputra, R. (2019, June). Study of the effect of load balance in 500 kVA distribution transformers in complex Pt. Perta Arun Gas area of 17 Dumai branch Lhokseumawe City. In IOP Conference Series: Materials Science and Engineering (Vol. 536, No. 1, p. 012053). IOP Publishing. https://doi.org/10.1088/1757-899X/536/1/012053

Wardhana, W., Azis, A., & Irwansi, Y. (2024). Analisa penurunan umur transformator akibat pengaruh pembebanan dan temperatur di PT PLN (Persero) P3B Sumatera UPT Palembang Gardu Induk Keramasan. Jurnal Surya Energy, 9(1), 46-57. https://doi.org/10.32502/jse.v9i1.283

Widagdo, R. S., & Andriawan, A. H. (2023). Analysis of losses due to load unbalance in a 2000 kVA transformer at Supermall Mansion 2 Tower Tanglin Surabaya. Journal of Engineering and Scientific Research, 5(2), 78-84. https://doi.org/10.23960/jesr.v5i2.144

Downloads

Published

2025-11-25

How to Cite

Azis, A., Perawati, Yudi Irwansi, & Muhammad Rizal. (2025). Analysis of the Impact of Load Imbalance on Neutral Current and Power Losses Caused by Neutral Current in Transformer 1, 30 MVA, 70/20 kV at Bungaran Substation. International Journal of Electrical Engineering, Mathematics and Computer Science, 2(3), 41–53. https://doi.org/10.62951/ijeemcs.v2i3.318